S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
35
65-0321—01
Actuator Standby Positions (Presets)
Fig. 67. Fuel Standby Positions Preset.
Program Standby Position
—Lets you set the position of the
actuators when the controller is in the standby position. For
each actuator, select
Closed
,
Lightoff
or
Open
. If you select
Open
, you must enter a value in the appropriate field to
indicate how wide the actuator should be opened (percentage
of the actuator span value).
Program Non Selected Fuel Position
—Lets you set the
position of the fuel actuator of the fuel that is not currently
being used. Select
Closed
,
Lightoff
or
Open
.
Remember to press the Set button before moving to a different
page.
Fig. 68. Fuel Standby Positions—Set Standby Open
Percentage.
Default System Parameters
The default values/settings for each system parameter are
shown in Table 5.
Advanced Options
Some advanced commissioning options are available by
selecting the “Advanced Options” button on the
Commissioning Configuration page (Fig. 69).
Fig. 69. Advanced Options.
Factory Default
To reset the Fuel/Air Ratio Control to factory default, select the
“Factory Default” button. A confirmation pop-up box displays
(Fig. 70) before the reset occurs. The user selects the “Yes”
button to continue with the reset. This feature is only enabled
for R7999 controllers that are build 180 and newer.
Table 5. Default Values/Settings for System Parameters
Parameter
Default
Xma Operation
Operation
Disabled
Max (20 mA)
NA
Min (4 mA)
NA
Threshold
NA
Differential
NA
Controller Timing
Postpurge time
30 seconds
Automanual Switch
Automanual Switch
Normal Mode
Program Standby Position
Fuel Selection 1
Fuel
Closed
Air
Closed
FGR
Closed
Fuel Selection 2
Fuel
Closed
Air
Closed
FGR
Closed
Program Non-Selected Fuel Position
Fuel Selection 1
Fuel Selection 2
Closed
Fuel Selection 2
Fuel Selection 1
Closed
FGR Behavior During Purge
FGR Behavior During Purge Remains Closed.
Table 5. Default Values/Settings for System Parameters
Parameter
Default
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...