S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY
29
65-0321—01
The user can choose to end the commissioning process before
everything is finished, and, if so, this page has the appearance
of the following two figures (Fig. 49 and 50), to indicate where
the user left off.
Fig. 49. Commission Configuration—uncompleted
commissioning view.
NOTE: Clicking the Home or Back or button will exit this
screen and display the Home page.
NOTE: Actuators that have completed their configuration
have a checkmark next to their button.
You must perform the following actions from this screen:
1.
Select base configuration for the system:
a. Base Configuration
(1)
Unconfigured
—This is the initial (default) option.
You can select this option to erase the current
configuration and reset to factory configuration.
(2)
Single Fuel
—Select if you want to configure only
one fuel actuator and one air actuator.
(3)
Single Fuel with FGR
—Select if you want to
configure a fuel actuator, an air actuator, and an
FGR actuator.
(4)
Dual Fuel
—Select if you want to configure two
fuel actuators and one air actuator.
(5)
Dual Fuel with FGR
—Select if you want to
configure two fuel actuators, one air actuator, and
an FGR actuator.
2.
Select and configure all actuators within the base
configuration:
b. Air
Fuel1
Fuel 2
FGR
(1) Press a button to configure the actuator. (If you
selected ‘Single Fuel’ or ‘Single Fuel with FGR’ in
the Base Configuration, the Fuel 2 button is not
displayed. If you selected ‘Single Fuel’ or ‘Dual
Fuel’ in the Base Configuration, the
FGR
button is
not displayed.) When you press a button, the
Set
Actuator Endpoints
screen is displayed. When
the actuator has been configured, a checkmark is
displayed next to the appropriate button. See Fig.
49.
3.
Go to the System Parameters screens to set system
parameters or view the default system parameters (If
necessary).
4.
Press the Next button to configure a ControLinks™
curve.
5.
Press Advanced Options Load Curve button to load and
configure a pre-existing ControLinks™ curve.
Fig. 50. Commissioning Configuration—completed
commissioning view.
Actuator Configuration
Selecting an actuator button displays a page like Fig. 51.
The direction that the actuator travels when it moves to its
closed position, and whether the actuator moves in fixed stops
or continuously rotates until it is told to stop, is selected on this
screen. Press the Next button when the settings are correct for
the actuator to advance to the next screen.
Fig. 51. Selecting Air Actuator type and travel direction.
Summary of Contents for S7999D1048
Page 70: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 70 ...
Page 72: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 72 ...
Page 74: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 65 0321 01 74 ...
Page 75: ...S7999D1048 COMBUSTION SYSTEM OPERATOR INTERFACE DISPLAY 75 65 0321 01 ...