Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9
reset time of the smoke detector.
A.3
Four-Wire Smoke Detectors/Devices (UL Listed)
Table A-3 Compatible Four-Wire Smoke Detectors
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
Model Name or Number
(Base model name or number in
parenthesis.)
Compatibility ID
# per Loop
Head
Base
Apollo
55000-350 (45681-200)
55000-350
45681-200
15 / loop
55000-250 (45681-200)
55000-250
45681-200
24 / loop
55000-225
55000-225
45681-255, 256
45681-200, 220, 232,
251, 252
15 / loop for Ion
Detectors
15 / loop for
Photo Electric
Detectors
55000-226
55000-226
55000-227
55000-227
55000-325
55000-325
55000-326
55000-326
55000-327
55000-327
55000-328
55000-328
Hochiki
SLR-24
HD-3
HSC-220R(HB-72)
NS6-220 OR NS4-220
(HB-3)
15 / loop
SLR-24H
SLR-24V
SLR-835
HD-3
14 / loop
SLR-835H
HD-5
System Sensor
1400
A
N/A
16 / loop
1451 (B401B)
A
N/A
16 / loop
2100
A
N/A
20 / loop
2100T
A
N/A
20 / loop
2151 (B401)
A
N/A
16 / loop
2151T (B401)
A
N/A
16 / loop
2400
A
N/A
16 / loop
2400TH
A
N/A
16 / loop
2451 (B401B)
A
N/A
16 / loop
2451TH (B401B)
A
N/A
16 / loop
2W-B
A
N/A
20 / loop
2WT-B
A
N/A
20 / loop
2WTA-B
A
N/A
20 / loop
2WTR-B
A
N/A
20 / loop
Smoke Detector/Base
Detector Type
Max Standby
Current (mA)
Alarm
Current (mA)
Fenwal CPD-7021 (w/70-201000-005 Base)
Ionization
0.10
*
Fenwal PSD-7125
Photoelectric
0.10
*
Fenwal PSD-7126 (w/70-201000-005 Base)
Photoelectric
0.10
*
Fire-Lite BLP-12-4W
Base
*
*
Gentex 824
Photoelectric
0.50
*
Gentex 824T
Photoelectric
0.50
*