LS10143-001SK-E
Programming
9-16
Select Type
UNUSED
B NOTIF
NOTIF OUTPUT
User also has Supervised/
Unsupervised option
CONTROL CIRCUIT
A NOTIF
Same as B NOTIF
AUX_PWR
CONSTANT
Constant auxiliary power.
AUX RESET
Resettable auxiliary power.
AUX DOOR
Door holder auxiliary power.
AUX SYNC
Select Type
B SWITCH
MANUAL PULL
Refer to comments column of
Table 9-4 for description of these options.
Latch or Non-latching feature only appears for
WATERFLOW, FIRE SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, ECS INPUT, ECS
TAMPER, and ECS SUPERVISORY.
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
User also has ECS Event Number 1-8 option for
ECS INPUT.
Only available when a ECS-VCM or ECS-
NVCM is installed in the system.
ECS TAMPER
ECS SUPERVISORY
A SWITCH
Same as B SWITCH
B DETECT
2-WIRE SMOKE
Used for Class B, 2-wire detectors.
4-WIRE SMOKE
Used for Class B, 4-wire detectors.
CO 4-WIRE DET
Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class B, 4-
wire CO Supervisory detectors
A DETECT
2-WIRE SMOKE
Used for Class A, 2-wire detectors.
4-WIRE SMOKE
Used for Class A, 4-wire detectors.
CO 4-WIRE DET
Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET
Latching or Non-latching used for Class A, 4-
wire CO Supervisory detectors
Select Zone/Group
Group or Zone selection will appear depending
on the type selected.
Edit Name
Table 9-6: Menu choices for Internal/External Power Module
Choices
Type Selections
Function
Selections for
each Type
Comments