LS10143-001SK-E
Control Panel Installation
4-34
2.
Configure the circuit through programming (see Section 9.5)
Figure 4-47 Class B Notification Appliance Circuit Wiring
Maximum voltage drop is 3V per Class B notification. See Table 4-4.
4.15.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1.
Wire the Class A notification appliances as shown in Figure 4-48.
Table 4-4: Maximum Impedance Class B
Current
Maximum Impedance
1.0A
3
Ω
1.5A
2
Ω
2.0A
1.5
Ω
2.5A
1.2
Ω
3.0A
1.0
Ω
Caution!
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput
connectors. Break wire runs to provide supervision of connections.
power limited supervised
notification wiring
regulated 24 VDC
3A per circuit, 9A max combined
4.7 k
Ω
EOL
alarm polarity shown