LS10143-001SK-E
Programming
9-10
6.
Select the type of device by pressing the up or down arrow key. Refer to Table 9-4 under the column heading
“Type Selection” for a list of choices.
Table 9-4: Programming Options for 5815XL Modules
Type
Selection
Function
Latching Option
Comments
UNUSED
Select for SLC points that are unused.
DETECTOR
PHOTO
Spot photoelectric detectors.
ION
Spot ionization detector.
HEAT
Spot heat detector.
PHOTO DUCT
Duct photoelectric detector.
ION DUCT
Duct Ion detector.
2-WIRE SMOKE
2-wire smoke detector.
SUP DET
PHOTO
Latching
Non Latching
Use this option when you want a detector to indicate a supervisory
alarm.
ION
HEAT
PHOTO DUCT
ION DUCT
SWITCH
MANUAL PULL
Use this switch type for manual pull stations. This input is always
latched. The switch can clear only when an alarm is reset. This
switch type has the highest fire priority; it overrides any other type of
fire alarm.
WATERFLOW
Latching
Use this switch type for monitoring water flow in a sprinkler system.
Switch closure will cause a sprinkler alarm. Water flow switches can
be programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a
water flow switch. The delay allows for normal, brief changes in
sprinkler system water pressure. The water flow alarm will not
activate unless the switch is active for the programmed delay time.
If a delay is used, the system begins counting down when the switch
closes. If the switch opens (restores) before the timer expires, a
water flow alarm is not generated. If the water flow switch remains
closed after the timer expires, a water flow alarm will be generated.
Non Latching
FIRE SUPER-
VISORY
Latching
Use this switch type for tamper monitoring of sprinklers and other
fire protection devices. If a contact closes, a sprinkler supervisory
event will be generated. Supervisory switches can be latching or
non-latching.
Non Latching
FIRE DRILL
System-level, non latching switch. This switch is an alternative way
of causing a fire drill. It has the same operation as the fire drill option
available from the annunciator. When the switch is activated, a fire
drill begins; when the switch is de-activated, the fire drill ends.
SILENCE
This system-level switch is an alternative way to silence the fire
system. It has the same effect as pressing the Silence key.
RESET
This system-level switch is an alternative way to reset the fire
system. It has the same effect as pressing the Reset key.