Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9-1
Section 9
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using the HFSS - Honeywell Fire Software Suite.
9.1
UL 864 / UL 2572 Programming Requirements
Important!
Before any customized programming is done, JumpStart AutoProgramming should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart
AutoProgramming is because JumpStart AutoProgramming automatically programs the system, searching for
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the hardware is properly
installed, custom programming can be performed. Refer to Section 8.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, and Stand for Mass Notifications
Systems, UL 2572, certain programming features or options must be limited to specific values or not used at all as
indicated below.
Programming
Option
Menu Item
Permitted in
UL 864
(Y/N)
Permitted in
UL 2572
(Y/N)
Possible
Settings
Settings
Permitted in UL
864
Settings
Permitted in
UL 2572
Time Options
Auto-resound
Yes
Yes
4 hrs, 24hrs
4 hours if using
SWIFT devices
4 hours if using
SWIFT devices
Time Options
Low AC
Report Delay
Yes
Yes
0–30 hours
1–3
1–3
Display Oldest
Event
Y (Enabled)
Yes
Yes
Yes & No
Yes
Yes
N (Disabled)
No
No
Yes & No
No
No
Initial Delay
0-28
Yes
Yes
0-28
3
3
Inter Message Delay 4-32
Yes
Yes
4-32
4-32
4-28
Alarm Verification
Alarm
Verification
Yes
Yes
60-250
(confirmation
period)
60
60
Auto Reset ECS
MIC Triggered Event
Auto Reset
ECS Custom
Event
Yes
Yes
Never
Timer Event
Disabled
Never
Timer Event
Disabled
Never
Timer Event
Disabled
ECS Input
ECS Input
Yes
Yes
Latching
Non-Latching
Latching
Latching
Event Priority
CO Alarm
No
No
Yes & No
No
No