Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9-21
9.6
System Options
This section of the manual explains how to customize software options that affect general operation of the
system. This includes such items as: Communication Options, Daytime/Nighttime Sensitivity, Holiday Days,
Time Options, Miscellaneous Options, Daylight Saving Options, Edit Banner, and SLC Family. Refer to each
individual subsection for complete instructions.
9.6.1
Communication Options
9.6.1.1 Auto Test Time
To access the Auto Test Time screen:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
From the next menu, select 1 for Communication Options.
ECS-VCM/ECS-RVM/
ECS/NVCM
UNUSED
SWITCH
MANUAL PULL
Refer to comments column of
Table 9-4 for description of these
options.
Latch or Non-latching feature only
appears for WATERFLOW, FIRE
SUPERVISORY, FIRE TAMPER, ZONE
AUX1, ZONE AUX2, SYSTEM AUX1,
SYSTEM AUX2, ECS INPUT, ECS
TAMPER, and ECS SUPERVISORY
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
User also has ECS Event Number 1-8
option for ECS INPUT.
Only available when an ECS-VCM or
ECS-NVCM is installed in the system to
the ECS-VCM or ECS-NVCM or ECS-
RVM choice part.
ECS TAMPER
ECS SUPERVISORY
VOICE AUX STATUS 1-2
BACKGROUND MUSIC
VOICE AUX ECS 1-4
Table 9-7 Choices for Point Programming Modules
Choices
Type Selections
Function Selections
for each Type
Comments