Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
3-3
B
SBUS2 OUT
SBUS communication
5 VDC
100 mA
0
Ω
A
+
SBUS power
24 VDC
1.0 A
-
B
SBUS2 IN
Used for Class A installations
0
Ω
A
+
-
N.C.
RELAY 1
General Purpose Relay 1
24 VDC
2.5 A, resistive
N/A
C
N.O.
N.C.
RELAY 2
General Purpose Relay 2
24 VDC
2.5 A, resistive
N/A
C
N.O.
N.C.
TROUBLE
Trouble Relay
24 VDC
2.5 A, resistive
N/A
C
N.O.
S-
SLC OUT
SLC terminals
32 VDC
150 mA
0
Ω
S+
SC-
SLC IN
Used for Class A installations
0
Ω
SC+
Ring
Phone Line 1 Telco Ring
N/A
0
Ω
Tip
Phone Line 1 Telco Tip
Ring
Phone Line 1 Premises Ring
Tip
Phone Line 1 Premises Tip
Ring
Phone Line 2 Telco Ring
N/A
0
Ω
Tip
Phone Line 2 Telco Tip
Ring
Phone Line 2 Premises Ring
Tip
Phone Line 2 Premises Tip
+
Battery
Battery Connection
24 VDC
1.12 A
N/A
–
P3
EXT. Comm
Cellular
Connection
B
input
0
Ω
A
S+
55 mA, 95 mA
S-
P7
Data
Network
Used for SK-NIC
24 VDC
21 mA
0
Ω
P8
Voice
Network
Used For ECS-NVCM
24 VDC
59 mA
0
Ω
Table 3-1 Terminal Descriptions and Electrical Specifications
Terminal Label
Description
Rating
Earth Ground
Faults
Voltage
Current
Summary of Contents for IFP-2100