LS10143-001SK-E
System Operation
10-12
Table 10-2: Operations Mode Behavior
Operation
Mode
Occurs When
System Behavior
In This Mode You Can
Normal
No alarm or
trouble condition
exists and
menus are not in
use.
SYSTEM POWER LED is on.
The All Systems Normal display indicates that
the system is in normal mode.
The current date and time display on the last
line of the LCD.
Enter the appropriate code to activate the User or
Installer Menu.
Alarm
A smoke
detector goes
into alarm or a
pull station is
activated.
The system seizes control and will the central
station.
The on-board annunciator will sound loud,
steady beeps to distinguish Alarm signals. For
Fire Alarm, the sequence is a loud steady
beep.(Any notification devices attached to the
system will also sound). For ECS Alarm, the
sequence is four seconds on, one second off.
GENERAL ALARM LED is on.
The LCD displays a screen similar to this one.
Press the down arrow to view the alarm. A screen
similar to this one displays.
Press SILENCE to silence the annunciator (and
any notification devices attached to the system).
When the alarm condition clears, press RESET to
restore the panel to normal.
If more than 3
categories are
active at a single
time and ECS is
enabled.