Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
4-39
2.
Smoke power is supplied to each Class A loop as shown in Figure 4-54.
Figure 4-54 Class A 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits are always referred to as the lowest Flexput
circuit number used. For example, Figure 4-54 uses Flexput circuits 1, 2, 3 together and 4, 5, 6 together.
In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be referred to as point 4.
4.15.5
Auxiliary Power Installation
Flexput Circuits 1-8 on the control panel can be used as auxiliary power circuits. The three types of auxiliary
power available are:
•
Door Holder Power (see Section 4.15.5.1)
•
Constant Power (see Section 4.15.5.2)
•
Resettable Power (see Section 4.15.5.3)
•
Sounder Sync Power (see Section 4.15.5.4)
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all Flexput circuits
must not exceed 9.0 A in alarm, and 6A when used as constant auxiliary power in normal standby).
To install an auxiliary power circuit:
1.
Wire the Flexput circuit(s) that will be used for auxiliary power. See Figure 4-55 for location of Flexput cir
-
cuits.
2.
Configure the auxiliary power output through programming (see Section 9.5).
Figure 4-55 Flexput Circuit Location
Air Products
PAM-2
Model 160150
Supervision
Module
supervised
power limited
Maximum Impedance per
circuit is 50
Ω
PAM-2
When used as auxiliary power, terminals labeled “O” are
negative, terminals labeled “X” are positive