Model IFP-2100/ECS Installation Manual
LS10143-001SK-E
9-27
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Select 5 for System Options.
4.
Select 4 for Time Options.
A screen similar to the one shown in Figure 9-14 will display.
Figure 9-14 Water Flow Delay Programming Screen
5.
Enter the number of seconds (0 to 90) to delay a water flow switch alarm, then press ENTER.
9.6.4.2 Alarm Verify
You can set the alarm verification time from 60 to 250 seconds (default is 60 seconds).
To set the alarm verification:
6.
Enter the desired number of seconds for the alarm verification time.
7.
Press right arrow key
or
ENTER to make your selection and move to the next programming option.
9.6.4.3 AC Report Delay
Note: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a low AC report will be sent to the central station.
To program low AC report delay, follow these steps:
Note: Steps continued from step 7 of Section 9.6.4.2.
8.
Enter the number of hours (0-30) before a low AC report will be sent to the central station, then press
ENTER.
9.6.4.4 Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Internal. AC Frequency feature dictates how the
control panel will calculate time based on the AC line frequency used in the installation site. The “Internal”
option can be used in areas where the AC line frequency is not dependable and you want the panel to calculate
time from the internal crystal. The internal crystal is not as accurate as the AC power source and internal 60 Hz
or 50 Hz should normally be selected. The panel defaults to the 60 Hz selection.
To change the AC line frequency:
9.
Select 50Hz, 60Hz or Intl, by pressing the up or down arrow key, then press ENTER.
9.6.4.5 Clock Format (AM/PM or Military)
To change the system clock display format:
10. Select AMPM (for AM/PM display format) or MIL (for military or 24 hr display format) by pressing the up
or down arrow key, then press ENTER.
Delay in seconds before waterflow
alarm occurs (00-90)