HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719
58
5.10
Group 3.10: Automatic reset
Table 27. Autoreset settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.10.1
Automatic reset
0
1
1
731
0 = Disabled.
1 = Enabled.
P3.10.2
Restart Function
0
1
1
719
0 = Flying start.
1 = According to P3.2.4.
P3.10.3
Wait Time
0.10
10000.00
s
0.50
717
P3.10.4
Trial Time
0.00
10000.00
s
60.00
718
P3.10.5
Number of Trials
1
10
4
759
P3.10.6
Autoreset:
Undervoltage
0
1
1
720
0 = No.
1 = Yes.
P3.10.7
Autoreset:
Overvoltage
0
1
1
721
0 = No.
1 = Yes.
P3.10.8
Autoreset: Overcurrent 0
1
1
722
0 = No.
1 = Yes.
P3.10.9
Autoreset: AI Low
0
1
1
723
0 = No.
1 = Yes.
P3.10.10
Autoreset: Unit
Overtemperature
0
1
1
724
0 = No.
1 = Yes.
P3.10.11
Autoreset: Motor
Overtemperature
0
1
1
725
0 = No.
1 = Yes.
P3.10.12
Autoreset: External
Fault
0
1
0
726
0 = No.
1 = Yes.
P3.10.13
Autoreset: Underload
Fault
0
1
0
738
0 = No.
1 = Yes.
P3.10.14
PID Supervision
0
1
0
15538
0 = No.
1 = Yes.
5.11
Group 3.11: Application Settings
Table 28. Settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.11.1
C /°F selection
0
1
0
1197
P3.11.2
kW/HP selection
0
1
0
1198
P3.11.3
LOC/REMButtonConfig
0
7
7
1195
P3.11.4
Password
0
9999
0
1900