HVAC400X – APPLICATION MANUAL
69
EN2B-0417GE51 R0719
5.17
Group 3.17: Fire Mode
Table 50. Fire mode parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.17.1 Fire Mode Password
0
9999
0
1599
1002 = Enabled.
1234 = Test mode.
P3.17.2 Fire Mode Activ. Open
DigINSlot0
.2
1596
Open = Fire Mode active.
closed = No action.
P3.17.3 Fire Mode active closed
DigINSlot0
.1
1619
Open = No action.
Closed = Fire Mode active.
P3.17.4 Fire Mode Frequency
8.00
P3.3.2
Hz
50.00
1598
P3.17.5
Fire Mode Frequency
Source
0
8
0
1617
0 = Fire Mode frequency.
1 = Preset speeds.
2 = Keypad.
3 = Fieldbus.
4 = AI1.
5 = AI2.
6 = AI1 + AI2.
7 = PID1.
8 = Motor potentiometer.
P3.17.6 Fire Mode Reverse
DigINSlot0
.1
1618
Open = Forward.
Closed = Reverse.
P3.17.7 Fire Mode preset freq. 1
0
50
10
15535
P3.17.8 Fire Mode preset freq. 2
0
50
Hz
20
15536
P3.17.9 Fire Mode preset freq. 3
0
50
30
15537
V3.17.10 Fire Mode Status
0
3
0
1597
A 0 = Disabled.
1 = Enabled.
2 = Activated (E DI
Open).
3 = Test Mode.
V3.17.11 Fire Mode Counter
0
1679
P3.17.12
Fire Mode Run Indication
Current
0.0
100.0
%
10.0
15580
5.18
Group 3.18: kWh Pulse Output Settings
Table 51. kWh pulse output settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.18.1 kWh pulse length
50
200
ms
50
15534
P3.18.2 kWh pulse resolution
1
100
KWh
1
15533