HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719
14
Table continued: Quick Setup parameter group
Index
Parameter
Min
Max
Unit
Default ID
Description
P1.12
Preset frequency 2
0.00
50.00
Hz
15.00
106
Select with the digital input: Preset
frequency selection 1 (P3.5.1.17)
(Default = Digital Input 5).
P1.13
Acceleration time 1
0.1
3000.0
s
5.0
103
Indicates the quantity of time that is
necessary for the output frequency to
increase from zero frequency to the
maximum frequency.
P1.14
Deceleration time 1
0.1
3000.0
s
5.0
104
Indicates the quantity of time that is
necessary for the output frequency to
decrease from the maximum frequency
to zero frequency.
P1.15
Remote control place 0
1
0
172
The selection of the remote control
place (start/stop).
0 = I/O control.
1 = Fieldbus control.
P1.16
Automatic reset
0
1
0
731
0 = Disabled.
1 = Enabled.
P1.17
Motor switch
0
1
0
653
0 = Disabled.
1 = Enabled.
P1.18
PID Mini-Wizard *
0
1
0
1803
0 = Disabled.
1 = Enabled.
See
2.1
PID Mini-Wizard.
P1.19
Pump and Fan
Cascade Wizard*
0
1
0
0 = Disabled.
1 = Enabled.
See
2.2 Pump and Fan Cascade Mini-
Wizard
.
P1.20
Fire Mode Wizard **
0
1
0
1672
0 = Disabled.
1 = Enabled.
P1.21
Start-Up Wizard **
0
1
0
1171
0 = Disabled.
1 = Enabled.
* = The parameter is visible only on the graphical keypad.
** = The parameter is visible only on the graphical and the text keypad.