HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719
46
5.4
Group 3.4: Ramp and Brakes Set-Up
Table 17. Ramp and brakes set-up
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.4.1
Ramp 1 Shape
0.0
10.0
s
0.0
500
P3.4.2
Acceleration Time 1
0.1
3000.0
s
5.0
103
P3.4.3
Deceleration Time 1
0.1
3000.0
s
5.0
104
P3.4.4
Ramp 2 Threshold
0.00
50.00
Hz
0.00
526
P3.4.5
Ramp 2 Shape
0.0
10.0
s
0.0
501
P3.4.6
Acceleration Time 2
0.1
3000.0
s
20.0
502
P3.4.7
Deceleration Time 2
0.1
3000.0
s
20.0
503
P3.4.8
Ramp Time Optimizer
0
1
0
1808
0 = Disabled.
1 = Enabled.
P3.4.9
Ramp Time Optimizer %
Step
0.00
50.0
10.0
1809
I.e., 10% of 60s ramp time
= a 6-second correction.
P3.4.10
Ramp Optimizer Max.
Time
0.1
3000.0
40.0
1810
P3.4.11
Start Magnetizing Time
0.00
600.00
s
0.00
516
P3.4.12
Start Magnetizing Current Varies
Varies
A
Varies
517
P3.4.13
DC Braking Time at Stop
0.00
600.00
s
0.00
508
P3.4.14
DC Brake Current
Varies
Varies
A
Varies
507
0 = Disabled.
P3.4.15
Frequency to Start DC
Braking at Ramp Stop
0.10
10.00
Hz
1.50
515
P3.4.16
Flux Braking
0
1
0
520
0 = Disabled.
1 = Enabled.
P3.4.17
Flux Braking Current
0
Varies
A
Varies
519