HVAC400X – APPLICATION MANUAL
43
EN2B-0417GE51 R0719
5.2
Group 3.2: Start / Stop Set-Up
Table 15. Start / stop menu
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.2.1
Remote Control Place
0
1
0
172
0 = I/O control.
1 = Fieldbus control.
P3.2.2
Local/Distance
0
1
0
211
0 = Remote.
1 = Local.
P3.2.3
Touche stop
0
1
1
1806
0 = Disabled.
1 = Enabled.
P3.2.4
Function Start
0
1
Varies
505
0 = Ramping.
1 = Flying start.
P3.2.5
Function Stop
0
1
0
506
0 = Coasting.
1 = Ramping.
P3.2.6
I/O A Start / Stop Logic
0
5
0
300
Logic = 0.
Ctrl signal 1 = Forward.
Ctrl signal 2 = Backward.
Logic = 1.
Ctrl signal 1 = Forward
(edge).
Ctrl signal 2 = Inverted
Stop.
Logic = 2.
Ctrl signal 1 = Forward
(edge).
Ctrl signal 2 = Backward
(front).
Logic = 3.
Ctrl signal 1 = Start.
Ctrl signal 2 = Inverted.
Logic = 4.
Ctrl signal 1 = Start (front).
Ctrl signal 2 = Backward.
Logic = 5.
Ctrl signal 1 = AI1
threshold.
Ctrl signal 2 = AI1
threshold.
P3.2.7
I/O B Start / Stop Logic
0
5
0
363
See above.
P3.2.8
AI1 Start Threshold
3.00
100.00
10.00
185
P3.2.9
Fieldbus Start Logic
0
1
0
889
A rising edge is necessary.
1 = State.
P3.2.10
Keypad Stop Button
No
Yes
No
114
No (Always enabled).
Yes = Start enabled only if
P3.2.2 is set to local.
P3.2.11
Start Delay
0.00
60.00
s
0.00
524