HVAC400X – APPLICATION MANUAL
57
EN2B-0417GE51 R0719
continued: Protections settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.15
Underload Fault (broken
belt/dry pump)
0
3
0
713
See P3.9.2.
P3.9.16
Underload Protection:
Field Weakening Area
Load
10.0
150.0
%
50.0
714
P3.9.17
Underload Protection:
Zero Frequency Load
5.0
150.0
%
10.0
715
P3.9.18
Underload Protection:
Time Limit
2.00
600.00 s
20.00
716
P3.9.19
Response to Fieldbus
Communication Fault
0
4
3
733
See P3.9.1.
P3.9.20
Slot Communication
Fault
0
3
2
734
See P3.9.2.
P3.9.21
Thermistor Fault
0
3
0
732
See P3.9.2.
P3.9.22
SoftFill Timeout
0
3
2
748
See P3.9.2.
P3.9.23
Response to PID1
Supervision Fault
0
3
2
749
See P3.9.2.
P3.9.24
Response to PID2
Supervision Fault
0
3
2
757
See P3.9.2.
P3.9.25
TempFault Signal
0
6
0
739
0 = Not Used.
1 = Temp. Input 1.
2 = Temp. Input 2.
3 = Temp. Input 3.
4 = Temp. Inputs 1-2.
5 = Temp. Inputs 2-3.
6 = Temp. Inputs 1-3.
P3.9.26
TempAlarm Limit
-30.0 °C
-22 °F
200 °C
392 °F
°C
°F
130.0 °C
266 °F
741
P3.9.27
TempFault Limit
-30.0 °C
-22 °F
200 °C
392 °F
°C
°F
155.0 °C
311 °F
742
P3.9.28
TempFault Response
0
3
2
740
0 = No response.
1 = Alarm.
2 = Fault (Stop according to stop
mode).
3 = Fault (Stop by coasting).