5.7
Group 3.7: Prohibit Frequencies
Table 24. Prohibit frequencies
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.7.1
Prohibit Frequency Range 1
Low Limit
-1.00
320.00
Hz
0.00
509
0 = Not used.
P3.7.2
Prohibit Frequency Range 1
High Limit
0.00
320.00
Hz
0.00
510
0 = Not used.
P3.7.3
Prohibit Frequency Range 2
Low Limit
0.00
320.00
Hz
0.00
511
0 = Not used.
P3.7.4
Prohibit Frequency Range 2
High Limit
0.00
320.00
Hz
0.00
512
0 = Not used.
P3.7.5
Prohibit Frequency Range 3
Low Limit
0.00
320.00
Hz
0.00
513
0 = Not used.
P3.7.6
Prohibit Frequency Range 3
High Limit
0.00
320.00
Hz
0.00
514
0 = Not used.
P3.7.7
Ramp Time Factor
0.1
10.0
Times
1.0
518
P3.7.8
Resonance Sweep Ramp
0.1
3000.0
s
60.0
1812
P3.7.9
Resonance Sweep
0
1
0
1811
0 = Disabled.
1 = Enabled.