HVAC400X – APPLICATION MANUAL
109
EN2B-0417GE51 R0719
Example:
Fig. 23. The digital inputs menu in the graphical display
Legend
A.
Name and function of the parameter.
B.
Digital input set for this parameter.
Six digital inputs are available in the standard I/O board compilation: the slot A terminals 8, 9, 10, 14, 15 and 16.
LOCATION OF THE I/O TERMINALS ON THE BOARDS
Input type
Slot
Input #
Explanation
DigIN
A
1
Digital input #1 (terminal 8) embedded in slot A (standard I/O board)
DigIN
A
2
Digital input #2 (terminal 9) embedded in slot A (standard I/O board)
DigIN
A
3
Digital input #3 (terminal 10) embedded in slot A (standard I/O board)
DigIN
A
4
Digital input #4 (terminal 14) embedded in slot A (standard I/O board)
DigIN
A
5
Digital input #5 (terminal 15) embedded in slot A (standard I/O board)
DigIN
A
6
Digital input #6 (terminal 16) embedded in slot A (standard I/O board)
The function External Fault Close, the location of which is the menu M3.5.1, is parameter P3.5.1.7. It gets the
default value DigIN SlotA.3 in the graphical display. By default, DI3 is selected and it will trigger a default if the
contact on terminal 10 is closed.
LOCATION OF THE I/O TERMINALS ON THE BOARDS
Parameter
Function
Default
ID
Description
P3.5.1.7
External Fault Close
DigINSlot.3
405
OPEN = OK
CLOSED = External fault
To change the input from DI3 to, e.g., DI6 (terminal 16) on the standard I/O, proceed according to the following
instructions.
STOP
Digital Inputs
ID: 405
Ext Fault Close
Ext Fault Open
Fault Reset Close
DigINSlotA.3
DigINSlot0.2
DigINSlotA.6
P3.5.1.7
READY
I/O
A
B