HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719
138
P3.12.1.5: Assign to channel: TimeChannel1.
Interval 2
P3.12.2.1: ON Time: 09:00:00.
P3.12.2.2: OFF Time: 13:00:00.
P3.12.2.3: From Day: Saturday.
P3.12.2.4: To Day: Sunday.
P3.12.2.5: Assign to channel: TimeChannel1.
Timer 1
You can start the motor with digital input 4 on slot A during times other than those specified with the intervals. In
this case, the timer specifies the duration that the motor runs.
P3.12.6.1: Duration: 1800 s (30 min).
P3.12.6.2: Assign to channel: TimeChannel1.
P3.5.1.19: Timer 1: DigIn SlotA.4 (The parameter located in the digital inputs menu).
Fig. 36. TimeChannel1 is used as the control signal for the
Start
command instead of a digital input
Legend
A.
Interval 1.
I.
ON = 09:00:00 hrs.
B.
From = Monday.
J.
OFF = 13:00:00 hrs.
C.
To Thursday.
K.
Digital input 1 on Slot A.
D.
ON = 07:00:00 hrs.
L.
Timer 1, Duration = 1800 s
E.
OFF = 17:00:00 hrs.
M.
Signal Ctrl 1A.
F.
Interval 2.
N.
TimeChannel1.
G.
From Saturday.
O.
Start/Stop.
H.
To Sunday.
P3.12.1.1 ON TIME (ID 1464)
You can use this parameter to set the time of day when the output of the interval function is activated.
Interval 1
Interval 2
From = Monday
From = Saturday
ON = 07:00:00 hrs
ON = 09:00:00 hrs
Digital input 1
on Slot A
To = Friday
To = Sunday
Time channel 1
Start/Stop
OFF = 17:00:00 hrs
OFF = 13:00:00 hrs
Timer 1
Duration = 1800 s
P Ctrl Signal 1A
A
F
M
N
H
E
C
J
L
B
G
D
I
K
O