HVAC400X – APPLICATION MANUAL
47
EN2B-0417GE51 R0719
5.5
Group 3.5: I/O Configuration
For more information, see
10.5.1.1
Programming Digital Inputs.
Table 18. Digital input settings
Index
Parameter
Min
Max
Unit
P3.5.1.1
Control signal 1 A
DigIN SlotA.1
403
P3.5.1.2
Control signal 2 A
DigIN SlotA.2
404
P3.5.1.3
Control signal 1 B
DigIN Slot0.1
423
P3.5.1.4
Control signal 2 B
DigIN Slot0.1
424
P3.5.1.5
I/O B Control Force
DigIN Slot0.1
425
P3.5.1.6
I/O B Reference Force
DigIN Slot0.1
343
P3.5.1.7
External Fault Close
DigIN SlotA.3
405
OPEN = OK.
CLOSED = External fault.
P3.5.1.8
External Fault Open
DigIN Slot0.2
406
OPEN = External fault.
CLOSED = OK.
P3.5.1.9
Fault Reset Close
DigIN SlotA.6
414
P3.5.1.10
Run Enable
DigIN Slot0.2
407
P3.5.1.11
Interlock 1
DigIN Slot0.2
1041
P3.5.1.12
Interlock 2
DigIN Slot0.2
1042
P3.5.1.13
Acceleration / Deceleration Time
Set
DigIN Slot0.1
408
OPEN = Ramp 1 Shape, Acceleration Time
1 and Deceleration Time 1.
CLOSED = Ramp 2 Shape, Acceleration
Time 2 and Deceleration Time 2.
P3.5.1.14
Motor Preheat ON
DigIN Slot0.1
1044
OPEN = No action.
CLOSED = Uses the DC current of the
motor preheat in Stop state. Used when the
value of P3.1.2.5 is 2.
P3.5.1.15
Fire Mode Activation OPEN
DigIN Slot0.2
1596
OPEN = Active.
CLOSED = Inactive.
P3.5.1.16
Preset Frequency Selection 0
DigIN SlotA.4
419
P3.5.1.17
Preset Frequency Selection 1
DigIN SlotA.5
420
P3.5.1.18
Preset Frequency Selection 2
DigIN Slot0.1
421
P3.5.1.19
Timer 1
DigIN Slot0.1
447
P3.5.1.20
Timer 2
DigIN Slot0.1
448
P3.5.1.21
Timer 3
DigIN Slot0.1
449
P3.5.1.22
PID1 Setpoint Boost
DigIN Slot0.1
1046
OPEN = No boost.
CLOSED = Boost.