PARAMETERS MENU
Table 12. Menu and Parameter group description
Menu and Parameter group
Description
Group 3.1: Motor settings
Basic and advanced motor settings.
Group 3.2: Start/Stop setup
Start and stop functions.
Group 3.3: Control reference settings
Frequency reference setup.
Group 3.4: Ramp & Brakes Setup
Acceleration/Deceleration setup.
Group 3.5: I/O Configuration
I/O programming.
Group 3.6: Fieldbus Data Mapping
Fieldbus data out parameters.
Group 3.7: Prohibit Frequencies
Prohibit frequencies programming.
Group 3.8: Limit supervisions
Programmable limit controllers.
Group 3.9: Protections
Protections configuration.
Group 3.10: Automatic reset
Auto reset after fault configuration.
Group 3.11 Application Settings
Settings of the process units, keypad, and passwords.
Group 3.12: Timer functions
Configuration of three timers based on Real-Time Clock.
Group 3.13: PID controller 1
Parameters for PID Controller 1. Motor control or external usage.
Group 3.14: PID controller 2
Parameters for PID Controller 2. External usage.
Group 3.15: Pump and Fan Cascade
Parameters for PFC system.
Group 3.16 Maintenance counters
Parameters for Maintenance counters.
Group 3.17: Fire mode
Parameters for Fire Mode.
Group 3.18 kWh Pulse Output
Parameters to configure a digital output giving pulses that agree with the kWh counter.
5.1
Group 3.1: Motor Settings
NOTE:
If drive is in the run state, these parameters are locked.
Table 13. Basic settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.1.1
Motor nominal voltage
Varies
Varies
V
Varies
110
P3.1.1.2
Motor nominal frequency 8.00
320.00 Hz
50 (60 in N.
America)
111
P3.1.1.3
Motor nominal speed
24
19200
rpm
1370 (1750 in N.
America)
112
P3.1.1.4
Motor nominal current
Varies
Varies
A
Varies
113
P3.1.1.5
Motor Cos Phi
0.30
1.00
Varies
120
P3.1.1.6
Motor Nominal Power
Varies
Varies
Kw/hp
Varies
116
P3.1.1.7
Motor current limit
Varies
Varies
A
Varies
107
P3.1.1.8
Motor type
0
1
0
650
0 = asynchronous induction
motor.
1 = PM synchronous motor.