Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
52
Table 20. Monitoring values
Code
Monitoring signal
Unit
ID
Description
V3.1
Drive status word
43
Bit codes status of drive
B0
= Ready
B1
= Run
B2
= Reverse
B3
= Fault
B6
= RunEnable
B7
= AlarmActive
B12
= RunRequest
B13
= MotorRegulatorActive
V3.2
Application status word
89
Bit codes status of application:
B3
= Ramp 2 Active
B5
= Remote CTRL Place 1 active
B6
= Remote CTRL Place 2 active
B7
= Fieldbus Control Active
B8
= Local Control Active
B9
= PC Control Active
B10
= Preset Frequencies Active
V3.3
DIN status word
56
Bit codes status of application:
B0
= DI1
B1
= DI2
B2
= DI3
B3
= DI4
B4
= DI5
B5
= DI6
B6
= DIE1
B7
= DIE2
B8
= DIE3
B9
= DIE4
B10
=DIE5
B11
=DIE6
V4.1
PID setpoint
%
20
Regulator setpoint
V4.2
PID feedback value
%
21
Regulator actual value
V4.3
PID error
%
22
Regulator error
V4.4
PID output
%
23
Regulator output
V4.5
Process
29
Scaled process variable see „P14.18“ on page 86
V5.1
Fire mode status
1597
0 = Disabled
1 = Enabled
2 = Activated (E DI Open)
3 = Test Mode
V5.2
Fire mode counter
1679
Fire mode counter tells how many times fire mode has been activated. This counter can not be reset.
V5.3
Warranty affected device
1682
1 = Device is warranty affected as critical faults triggered in fire mode
0 = Normal device
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...