Table 22. Motor settings
Code Parameter
Min
Max
Unit
Default
ID
Note
P1.17 Motor identification
0
1
0
631
0
= not active
1
= standstill identification
( need run command within 20 s to activate)
2
= ID with run
P1.18 Rs voltage drop
0,00
100,00
%
0,00
662
Voltage drop over motor windings as % of Un at
nominal current. This parameter is adjusted auto-
matically when Identification run is performed.
P1.19 Overvoltage controller
0
2
1
607
0
= Disabled
1
= Enabled: default mode
2
= Enabled: shock load mode
P1.20 Undervoltage controller
0
1
1
608
0
= Disable
1
= Enabled
P1.21 Sine filter
0
1
0
522
0
= Not in use
1
= In use
P1.22 Modulator type
feature not used,
leave at default
0
65535
28928
648
Bit 1
= Discontinuous modulation
Bit 2
= Pulse dropping in over modulation
Bit 6
= Under modulation
Bit 8
= Instantaneous DC voltage compensation
Bit 11
= Low noise
Bit 12
= Dead time compensation
Bit 13
= Flex error compensation
P1.23 Energy optimization
0
1
0
666
Energy optimization, the frequency converter
searches for the minimum current in order to save
energy and lower motor noise:
0
= Disabled
1
= Enable
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...