9.1.15 Motor Pre-heat (Control panel: Menu PAR
P15)
Table 36. Motor Pre-heat.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P15.1
PreHeat function
0
3-4 *
0
1225
0
= not used
1
= always in stop state
2
= controlled by digital input
3
= heatsink temperature limit
4
= external temperature limit
P15.2
PreHeat current
0
50%
motor
nominal
current
A
0
1227
Motor pre heat current
P15.3
Heatsink temperature limit
-10
80
°C
40
1620
Heatsink temperature to stop pre heat
P15.4** External temperature
selection
0
7
1
1621
Selection of external temperature
0
= None of the temperature inputs are selected
1
= Temperature input 1 selected
2
= Temperature input 2 selected
3
= Temperature input 1 and 2 selected
4
= Temperature input 3 selected
5
= Temperature input 1 and 3 selected
6
= Temperature input 2 and 3 selected
7
= Temperature input 1, 2 and 3 selected
P15.5** External temperature limit
-50.0***
200.0***
°C***
30.0
1622
External temperature to stop pre heat
* value 4 only if expansion OPTB2 is installed
** visible only if expansion OPTB2 is installed
*** unit and values depends on P16.3 Temperature unit
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...