Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
81
9.1.12 Protections (Control panel: Menu PAR
P12)
Table 33. Protections.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P12.1
Analogue Input low fault
0
4
1
700
0 = No action
1
= Alarm
2
= Alarm, preset alarm frequency
3
= Fault: Stop function
4
= Fault: Coast
P12.2
Under voltage fault
1
2
2
727
1
=
No response (no fault generated
but drive still stops modulation)
2
=
Fault: Coast
P12.3
Earth fault
0
3
2
703
0
= No action
1
= Alarm
2
= Fault: Stop function
3
= Fault: Coast
P12.4
Output Phase Fault
0
3
2
702
As parameter 12.3
P12.5
Stall protection
0
3
0
709
As parameter 12.3
P12.6
Under load protection
0
3
0
713
As parameter 12.3
P12.7
Motor thermal protection
0
3
2
704
As parameter 12.3
P12.8
Mtp: Ambient temperature
–20
100
°C
40
705
Environment temperature
P12.9
Mtp: Zero speed cooling
0,0
150,0
%
40,0
706
Cooling in % at zero speed
P12.10 Mtp: Thermal time constant
1
200
min
Varies
707
Thermal time constant of the engine
P12.11 Stall Current
0,00
2,0 × I
Nunit
A
I
Nunit
710
The engine is in stall, when the current
exceeds this limit
P12.12 Stall time
0,00
300,0
s
15,00
711
Blocking time
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...