Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
139
Control
characteristics
Control method
Frequency Control U/f
Open Loop Sensorless Vector Control
Switching frequency
1 … 16 kHz; Factory default 4 kHz
Frequency reference
Resolution 0.01 Hz
Field weakening point
30 … 320 Hz
Acceleration time
0.1 … 3000 sec
Deceleration time
0.1 … 3000 sec
Braking torque
100% × T
N
with brake option (only in 3~ drives sizes MI2-5)
30% × T
N
without brake option
Ambient
conditions
Ambient operating tem-
perature
14 °F (–10 °C) (no frost) … +104/122 °F (+40/50 °C) (depends on the unit size): rated loadability I
N
Side by side installation for MI1-3 it is always 104 °F (40 °C);
For IP21/Nema1 option in MI1-3 the maximum temperature is also 104 °F (40 °C)
Storage temperature
–40 °F (-40 °C) … +158 °F (70 °C)
Relative humidity
0 … 95% RH, non-condensing, non-corrosive, no dripping water
Air quality:
• chemical vapours
• mech. particles
• IEC 721-3-3, unit in operation, class 3C2
• IEC 721-3-3, unit in operation, class 3S2
Altitude
• 100% load capacity (no derating) up to 3281 ft. (1000 m).
• 1% derating for each 328 ft. (100 m) above 3281 ft. (1000 m);
• max. 6562 ft. (2000 m)
Vibration:
EN60068-2-6
• 3 … 150 Hz
• displacement amplitude 1(peak) mm at 3 … 15.8 Hz max
• acceleration amplitude 1 G at 15.8 … 150 Hz
Shock
IEC 68-2-27
• UPS Drop Test (for applicable UPS weights)
• Storage and shipping: max 15 G, 11 ms (in package)
Enclosure class
IP20 for MI1-3, IP21 for MI4-5 or MI-1-3 with accessory COMP-IP21-KIT# / COMP-NEMA1-KIT#
Pollution degree
PD2
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...