Table 33. Protections.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P12.25 Temperature fault input
1
7
1
739
Binary-coded selection of signals to use
for alarm and fault triggering
B0
= Temperature input 1
B1
= Temperature input 2
B2
= Temperature input 3
NOTE!
Hidden until an OPTBH
board is connected.
P12.26 Temperature fault mode
0
2
2
743
0
= Not used
1
= Low limit
2
= High limit
P12.27 Temperature fault limit
–50.0C/273.2 K
200,0/473,2
100,0
742
Temperature fault threshold, hidden
until an OPTBH board is connected
P12.28 Input phase fault
0
3
3
730
0 = No action
1
= Alarm
2
= Fault: Stop function
3
= Fault: Coast
P12.29 Motor temperature memory
mode
0
2
0
15521
0
= Disabled
1
= Constant mode
2
= Last value mode
NOTE:
These parameters are shown, when P16.2 = 0.