Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
56
9.1
Quick setup parameters (Virtual menu, shows when par. 16.2
1)
Table 21. Quick setup parameters.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.1
Motor nominal voltage
180
480
V
Varies
110
P1.2
Motor nominal frequency
30,00
320,00
Hz
50,00/60,00
111
P1.3
Motor nominal speed
30
20000
rpm
1440/1720
112
P1.4
Motor nominal current
0,2 × I
Nunit
2,0 × I
Nunit
A
I
Nunit
113
P1.5
Motor cos j (Power Factor)
0,30
1,00
0,85
120
P1.7
Current limit
0,2 × I
Nunit
2,0 × I
Nunit
A
1,5 × I
Nunit
107
P1.15 Torque boost
0
1
0
109
P1.23 Energy optimization
0
1
0
666
Energy optimization, the frequency con-
verter search for the minimum current
in order to save energy and lower motor
noise.
P2.1
Remote control place 1
0
2
0
172
P2.2
Start function
0
1
0
505
P2.3
Stop function
0
1
0
506
P3.1
Min frequency
0,00
P3.2
Hz
0.00
101
P3.2
Max frequency
P3.1
320,00 Hz
Hz
50,00/60,00
102
P3.3
Remote control place 1
frequency reference
selection
1
Varies
7
117
P3.4
Preset speed 0
P3.1
P3.2
Hz
5,00
180
P3.5
Preset speed 1
P3.1
P3.2
Hz
10,00
105
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...