Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
68
9.1.4 Ramps and brakes setup (Control panel: Menu PAR
P4)
Table 25. Ramps and brakes setup.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P4.1
Ramp S-shape 1
0,0
10,0
s
0,0
500
P4.2
Acceleration time 1
0,1
3000,0
s
3,0
103
P4.3
Deceleration time 1
0,1
3000,0
s
3,0
104
P4.4
Ramp S-shape 2
0,0
10,0
s
0,0
501
P4.5
Acceleration time 2
0,1
3000,0
s
10,0
502
P4.6
Deceleration time 2
0,1
3000,0
s
10,0
503
P4.7
Flux Braking
0
3
0
520
0
= Off
1
= Deceleration
2
= Chopper
3
= Full mode
P4.8
Flux Braking Current
0,5 × I
Nunit
2,0 × I
Nunit
A
I
Nunit
519
P4.9
DC Braking Current
0,3 × I
Nunit
2,0 × I
Nunit
A
I
Nunit
507
P4.10
Stop DC current time
0,00
600,00
s
0,00
508
0
= Not active
P4.11
Stop DC current frequency
0,10
10,00
Hz
1,50
515
P4.12
Start DC current time
0,00
600,00
s
0,00
516
P4.13
Accel2 Frequency Threshold
0,00
P3.2
Hz
0,00
527
0,00
= Disabled
P4.14
Decel2 Frequency Threshold
0,00
P3.2
Hz
0,00
528
0,00
= Disabled
P4.15
External Brake: Open Delay
0,00
320,00
s
0,20
1544
P4.16
External Brake: Open
Frequency limit
0,00
P3.2
Hz
1,50
1535
P4.17
External Brake : Close
Frequency limit
0,00
P3.2
Hz
1,00
1539
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...