9.1.8 Analogue outputs (Control panel: Menu PAR
P8)
Table 29. Analogue outputs.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P8.1
Analogue output signal
selection
0
14
1
307
0
= Not used
1
= Output freq. (0…f
max
)
2
= Output current (0…InMotor)
3
= Motor torque (0…T
nMotor
)
4
= PID output (0…100%)
5
= Freq. refer. (0…f
max
)
6
= Motor speed (0…n
max
)
7
= Motor power (0…P
nMotor
)
8
= Motor Voltage (0…U
nMotor
)
9
= DC-link Voltage (0…1 000 V)
10
= Process Data In1 (0…10 000)
11
= Process Data In2 (0…10 000)
12
= Process Data In3 (0…10 000)
13
= Process Data In4 (0…10 000)
14
= Test 100%
P8.2
Analogue output minimum
0
1
0
310
0
= 0 V / 0 mA
1
= 2 V / 4 mA
P8.3
Analogue output scaling
0,0
1000,0
%
100,0
311
P8.4
Analogue output filter time
0,00
10,00
s
0,10
308
P8.5
Analogue output E1 -
signal selection
0
14
0
472
As parameter P8.1,
hidden until an option board is connected
P8.6
Analogue output E1 -
minimum
0
1
0
475
As parameter P8.2,
hidden until an option board is connected
P8.7
Analogue output E1 -
scaling
0,0
1000,0
%
100,0
476
As parameter P8.3,
hidden until an option board is connected
P8.8
Analogue output E1 -
filter time
0,00
10,00
s
0,10
473
As parameter P8.4,
hidden until an option board is connected
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...