Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
91
Table 38. Fire mode.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P18.3
Fire mode:
frequency preset
P3.1
P3.2
Hz
8.00
1598
Fire mode frequency preset
NOTE!
This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
P18.4
Fire mode activation:
close
0
Varies
6
1619
Digital input, if fire mode is enable or in test mode then when
digital input is closed, fire mode will be active.
As parameter 5.1
NOTE!
This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
P18.5
Fire mode activation:
open
0
Varies
0
1596
Digital input, if fire mode is enable or in test mode then when
digital input is open, fire mode will be active.
As parameter 5.1
NOTE!
This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
P18.6
Fire mode:
reverse
0
Varies
0
1618
Reverse command of rotation direction while running in fire
mode. This DI has no effect in normal operation.
As parameter 5.1
NOTE!
This parameter will be locked when password for
fire mode is activated (not in the test mode), and not
only when fire mode input is set. To change the parame-
ter you have to disable fire mode.
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...