Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
86
Table 35. PID control parameters.
Code
Parameter
Min
Max
Unit
Default
ID
Note
P14.7
P gain
0,0
1000,0
%
100,0
118
Proportional gain
P14.8
I time
0,00
320,00
s
10,0
119
Integrative time
P14.9
D time
0,00
10,00
s
0,00
132
Derivative time
P14.10 Error inversion
0
1
0
340
0
= Direct
1
= Inverted
P14.11 Sleep minimum frequency
0,00
P3.2
Hz
25,00
1016
Threshold for enter sleep
P14.12 Sleep delay
0
3600
s
30
1017
Delay for enter sleep
P14.13 Wake up level
0,0
100,0
%
90
1018
Threshold for exit sleep
P14.14 Sleep setpoint boost
0,0
50,0
%
10,0
1071
Referred to setpoint
P14.15 Setpoint boost time
0
60
s
10
1072
Boost time after P14.12
P14.16 Sleep maximum loss
0,0
50,0
%
5,0
1509
Referred to feedback value after boost
P14.17
Sleep loss check time
1
300
s
30
1510
After boost time P14.15
P14.18 Process unit source select
0
5
0
1513
0
= PID feedback value
1
= Output frequency
2
= Motor speed
3
= Motor torque
4
= Motor power
5
= Motor current
P14.19 Process unit decimal digits
0
3
1
1035
Decimals on display
P14.20 Process unit minimum value
0,0
P14.21
0,0
1033
Process min value
P14.21 Process unit maximum value
P14.20
3200,0
100,0
1034
Process max value
Summary of Contents for HVAC232 Series
Page 1: ...APPLICATION MANUAL HVAC232 402 27 652_ENG06 ...
Page 60: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 60 ...
Page 64: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 64 ...
Page 95: ...Application manual HVAC232 402 Document 27 652 Issue ENG06 2019 08 07 95 ...