Device checks
"
Ensure all dust covers have been removed from the sensor heads and the system is allowed to operate for at
least 24 hours to obtain accurate time average and condition code readings.
Checking the time averages
You can manually recover card data. The following
procedure assumes there is no password access
required. Press the
Menu On/Off
button and then
[Info],
momentarily press
<etc>
to select
[Time
Avg]
and type in the channel number from the
range 1-6, select
[Device]
and type in the device
number for which the time average is required,
select
[Loop]
and type in the loop number of the
device ->
[Enter].
The display shows time averages for the device.
Foreground (fast) time average readings
Background (slow) time average readings
Tnew
T1
T2
T3
T4
T5
T6
T7
T8
T9
T10
T11
On
demand
80mS 320mS 1.28S 5.12S 20.48S
1.36min
5.46min
21.84min 1.45hr 5.82hr
23.3hr
Normally reads 252, unless there is a
threshold.
Device type 34K
Analogue Channel
number
Time average
Tnew
Optical
Heat
1
2
200 - 235
180 - 210
Heat
180 - 210
Beam Transmit
0
Beam Receive
2
150 - 170
Device type S-Quad
Analogue Channels
Time average Tnew
Heat Sensor
2 - heat
66
Heat Sensor Sounder
2 - heat
66
Dual Optical Heat Sensor
1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Strobe
1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Sounder
1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor Speech Strobe
1 - optical (forward)
2 - heat
4 - optical (backward)
25
66
40
Dual Optical Heat Sensor CO
1 - optical (forward)
2 - heat
3 - CO
4 - optical (backward)
25
66
25
40
Dual Optical Heat Sensor CO Speech Strobe
1 - optical (forward)
2 - heat
3 - CO
4 - optical (backward)
25
66
25
40
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
51
Vigilon (EN & BS) Compact (VA) panels
Device
checks
Average Channel 1 Device 1 Loop 1
19
252
252
252
252
252
19 19 19 19 18 18
Time average readings of Channel 1 device 1 loop 1
23:15
Tnew (On demand)
Background (slow) Time
average readings T6 of T11
Channel 1 Device 1 loop 1
Foreground (fast) Time
average readings T1 to T5 of
Channel 1 Device 1 loop 1
e Aver channel 1 Device 1 Loop 1
[Repeat]
[Previous]
[Next]
[Cancel]