
Wiring of external circuits
¨
With the exception of the mains cable, ensure the
following external circuit cables are left disconnected
at this stage of commissioning:
•
loop circuits
•
clean contacts
•
auxiliary circuits
•
master alarms (the end-of-line resistor (10K Ohm)
should be fitted to inhibit a master alarm circuit
fault indication).
•
Monitored input (the end-of-line resistor (10K
Ohm) should be fitted to inhibit a monitored input
fault indication).
&
Ensure the mains cable is securely
connected to the mains terminal block on the Power
supply unit (PSU).
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
27
Vigilon (EN & BS) Compact (VA) panels
Vigilon
C
ompact
Panel
PB15
REPEAT
INDICATOR
RS-485
24V
B
A
0V
Master Control Board
PB8
MASTER ALARMS
MA1+ MA1- MA2+ MA2-
PB9
MONITORED INPUT
and CLEAN CONTACTS
0V MIPNC C NO
PB10
AUXILIARY RELAY 1
PB7
LOOP 1
L1 0V L2 0V
PB14
LOOP 2
L1 0V L2 0V
NC C NO NC C NO
NC C NO
PB11
AUXILIARY RELAY 2
PB6
RS-232
TX1 RX1 0V TX2 RX2
BATT3
PB15
PB6
PB9
P2
CARD 1
IC3
KEYBOARD
IC16
POWER
SUPPLY
P12
MA2 - FS2 250mA
MA1 - FS1 250mA
P1
CARD 2
P16
P13
SW1
RESET
24V
B
A
0V
TX1 RX1 0V
PB8
MA1+ MA1- MA2+ MA2-
0V MIPNC C NO
FIRMWARE BACKUP
PB10
PB7
L1 0V L2 0V
24V
FS3 200mA
TX2 RX2
PB14
L1 0V L2 0V
NC C NO NC C NO NC C NO
PB11
SW2
MODE