Backplane slot and switch location on a
Fibre Optics Network card
"
The fibre optic network cards are factory set
for 38.4K baud with node address 4.
Switch settings
Node Address and switch settings
Switch settings and Baud rate
1
2
3
4
5
6
7
8
64
off
off
off
off
off
off
off
off
19.2K
1
on
off
off
off
off
off
on
off
38.4K
2
off
on
off
off
off
off
off
on
115.2K
3
on
on
off
off
off
off
on
on
230.4K
4
off
off
on
off
off
off
63
on
on
on
on
on
on
- Factory settings
Installation instructions
new fibre Network Card (EN)
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
oblication to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK
Website: www.gent.co.uk
Tel44 (0) 116 246 2000
Fax (UK): +44 (0)116 246 2300
Registered office: Novar House: 24 Queens Road, Weybridge, Surrey KT13 9UX
2
new fibre Network Card (EN) 4188-790 issue 2_07/06
by Honeywell
Fibre Optics Network Card
C
8
7654321
C87654321
BAUD
ADDRESS
On
Off
To DKC
40 way ribbon
cable
20 way ribbon
cable
Local Controller card
Input/Output card
Loop Processor card
Space for 3 Loop
Processors
Network card
P1
P4
LCC - P1
IOC- P2
LOOP 1 - P3
LOOP 2 - P4
LOOP 3 - P5
LOOP 4 - P6
P7
P8
Backplane
SW1
MCC/