How to configure the monitored input
The monitored input at the fire panel is activated by an external
switch installed maximum of 100m cable distance away from the
fire panel. The input is monitored for both short and open circuit
faults. When the input is active it triggers command build number
250 of the fire panel.
Example
The following example shows how to configure the monitored
input at the panel to provide an output sound signal 1 alarms in
sector 2 of loop 1 as a reversible action. This means on operating
or "closing" the monitored input the panel will start alarms in
sector 1 and on releasing or "opening" the monitored input the
panel will stop the alarms.
The following procedures assume a password entry is not
required.
Press
Menu On/Off
button and select
[SetUp]
, momentarily
press
<etc>
to select
[SetUp]
->
[Build]
and type in the
command build number
250
, select
[Action]
->
[UserCode]
,
momentarily press
<etc>
to select
[Sector],
type in
2
for sector 2
and select
[Loop]
and type in
1
for Loop 1 ->
[Action]
->
[Signal
1]
->
[Enter]
->
[reversb]
->
[Enter]
.
How to configure the buttons U1 and U2
"
The U1 and U2 buttons are active at access
level 2, that is access to the buttons is possible by
opening the panel door.
On operating the U1 or U2 at the panel it will cause triggering of
command build number 251 (for button U1) or command build
number 252 (for button U2). During commissioning the required
command build action must be configured.
Example
This example shows how to configure the U1 button such that
pressing it will start the master alarm sounders and pressing
Silence alarm
button will stop the sounders.
The following procedures assume a password entry is not
required.
Press
Menu On/Off
button and select
[SetUp]
, momentarily
press
<etc>
to select
[SetUp]
->
[Build]
and type in the
command build number
251
, select
[Action]
->
[Start MA]
->
[Enter]
->
[Non Reversbl]
->
[Enter]
. The U1 button is now
configured to start the master alarm sounders.
Example 2
This example shows how to configure the U1 button such that it
operates an output of an interface unit and releasing the U1
button it returns the output to normal condition.
The following procedures assume a password entry is not
required.
Press
Menu On/Off
button and select
[SetUp]
, momentarily
press
<etc>
to select
[SetUp]
->
[Build]
and type in the
command build number
251
, select
[Action]
->
[Usercode]
and
momentarily press
<etc>
to select ->
[Digital]
and type in the
interface output channel number, select
[On]
and type in the
interface device number, select
[Loop]
and type in the loop
number ->
[Enter]
, now select
[Reversb]
and then
[Enter]
. The
U1 button is now configured to switch on the digital output on an
interface unit and on releasing it will switch off the output.
How to configure LEDs CB253 and
CB254
The switching of the LEDs CB253 and CB254 result from
actioning on command builds 253 and 254 respectively. The
switching action must be configured during commissioning.
This example shows how to configure the panel such that by
activating an interface input (can be a push button switch), it will
cause the panel LED - CB253 and Master alarms to switch
On
. If
the interface input is released then the panel LED-CB253 and
Master alarms will switch
Off
.
The following procedures assume a password entry is not
required.
Example:
Press
Menu On/Off
button and select
[SetUp]
, momentarily
press
<etc>
to select
[SetUp]
->
[Build]
and type in the
command build number
253
, select
[Trigger]
->
[IO line]
and
type in the interface input channel number, select
[Device]
and
type in the interface device number, select
[Loop]
and type in
the loop number ->
[Enter]
. The command build 253 is now
configured to be triggered by the interface input.
Now to configure the command build label:
Press
Menu On/Off
button and select
[SetUp]
, momentarily
press
<etc>
to select
[SetUp]
->
[Build]
and type in the
command build number
253
, select
[Label]
and enter a label of
up to 40 character in length, select either
[Display]
to display the
label on the panel when the command build
253
is triggered.
Now to setup the action of command build 253:
Press
Menu On/Off
button and select
[SetUp]
, momentarily
press
<etc>
to select
[SetUp]
->
[Build]
and type in the
command build number
253
, select
[Actionl
->
[Start MA]
->
[Enter]
->
[Reversbl]
and
[Enter]
.
Generic Commissioning instructions
30
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Vigilon
C
ompact
Panel
P8
0V MIP
PANEL
2 - 10K Ohms -
resistors must be
fitted as shown.
MASTER CONTROL
BOARD
Normally open contacts
An active input will trigger
the command build No 250
The command build action
is configured
during commissioning
Monitored Input
These contacts can be a push button
switch, fire relay contacts from another
panel or contacts from a timer.