Message
associated with..
meaning..
..possible action
Interface Input
OC / restored
Device
The end-of-line is not seen.
Check the wiring. The device
may have been removed, if so
refit the device to restore.
Interface input
operated /
released
number x on loop
y channel z
Device
Fixed extinguishant
interface unit input has
been triggered.
Follow the FE system reset
procedure to release the
input.
Interface input
SC / restored
number x on
loop y channel z
Device
The interface wiring is
short circuit. The value of
input is equal to or less
than 2V.
Check the interface wiring
and rectify to restore the
input.
Interface output
SC or OC or
Restored number
x on loop y
channel y
Device
The value of output is
equal to or less than 50%
for SC
or is TBA for OC.
Check the wiring and restore
the output circuit.
Intermittent
Fault at card x
Any Card
A fault has been picked up
by the MCC / MCB (main
control card/board).
Replace the appropriate card
if the fault keeps reoccurring.
Invalid
configuration
Loop Processor Card
Loop recovered with
freeblocks ON.
This is not allowed. Switch
OFF the freeblocks and
reallocate.
Device
FLASH incorrectly
programmed
Replace the device
Invalid
configuration at
card x
Loop Processor
Card
Loop recovered with
freeblocks ON.
This is not allowed. Switch
OFF the freeblocks and
reallocate.
Invalid message
/ reply received
at card x
Loop Processor
Card
The message/reply received
cannot be understood. The
communication can be
from a Repeat, Mimic,
Supervisor, Network or
Orator system.
Ignore single occurrence and
record in log book.
Invalid
message/reply at
card x
Network Card
The message/reply has not
been understood from other
panels.
Ignore for single occurrence
and record in log book.
Invalid task
delay at card x
Any Card
Software error.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Invalid task
stage
Any Card
Software error.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
IO line Enabled
/ Disabled at
Card x
Loop Processor
Card
The IO line is either
enabled or disabled
automatically or manually.
If necessary, manually
enable/disable the IO line
using the [control] menu.
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
105
Vigilon (EN & BS) Compact (VA) panels
Appendix
B
-
M
essage
A
ction
L
ist