VIG-BEAM Beam sensor
Preparation
To commission the beam sensor pair check the following:
q
The control panel Loop processor and Local controller cards have
software version 3.4x or later.
NOTE:
The VIG-BEAM Beam sensor is a Type 3 sensor and it is SAFE
compatible.
q
The beam transmitter and receiver heads are installed on the same loop
circuit.
q
A two way radio is available for communication, while one person
aligns the beam sensor head, another person operates the controls and
read measurements given at the control panel.
The terms ‘head, device and outstation’ are used interchangeably.
These procedures assume the heads are mounted on the angle brackets.
Similar procedures are applicable for the IP rated and parallel brackets.
Identification
q
The beam sensor heads each has a black plastic circular label
surrounding the lens for identification.
q
The 2-way base has is a black plastic cover fitted over the electronics.
VIG-BEAM Beam sensor
Preparation
Vigilon Sys tem Com mis sioning
Figure 6-1
Beam sensor
pair and
brackets
cdn473