This new Input Output (IO) card (
part no. VIG-IOC-DOM)
is
designed for installation in EN54 Vigilon analogue addressable
fire panels and Network node:
Vigilon Fire Panels
•
VIG1
•
VIG1-NET
•
VIG2
•
VIG2-NET
•
VIG3
•
VIG3-NET
•
VIG4
•
VIG4-NET
Vigilon Network (Terminal) Node
•
VIG-NODE.
new IO card replaces existing IO cards
The new IO card combines the functions of and will replace the
existing IO cards:
•
VIG-IOC-PRT
•
VIG-IOC-ASCOM
•
VIG-IOC-UFD
•
VIG-IOC-UNI
The existing IO cards are no longer available.
Specification
Overall size
148mm height x 100mm
width
Node address range
1 to 31
Baud
(When installed as an
additional IO card)
1200, 1800, 2400, 3600,
4800, 7200, 9600 and 19200
RS232 (Port 0)
RS485 (Port 1)
10m cable distance
1.2Km cable distance
Weight
72g (approximate)
Operating temperature 0
°
C to 45
°
C
Storage temperature
-10
°
C to 55
°
C
Relative humidity
(non condenscing)
up to 90%
"
There is no need to switch between the
RS232 and RS485 ports as they are both available for
simultaneous use.
IO card installation and associated
terminals
The diagram below shows the associated terminals for
standard IO card when it is installed in the backplane of
panel/node.
Checks
¨
Set the rotary switch
SW2
to a required function.
¨
Ensure all DIP switches
SW1
are set to the Off
position before installing the IO card in socket
P2
of
the backplane
¨
Connect the 20 way ribbon cable from DKC
connector
P4
to the IO card socket
P2
.
¨
One additional IO card can be fitted into the
backplane spare socket
P7
of the control panel and
up to four into the backplane sockets of the Network
node.
When installing an additional IO card it is important
to set its DIP switches
SW1
to the required baud rate
and node address and the rotary switch
SW2
to the
required function before installing the card in a spare
socket of the backplane.
new IO Card (EN54) 4188-777 issue 3_11/05
1
Installation instructions
new IO Card (EN54)
(VIG-IOC-DOM)
by Honeywell
Tx CTS RxRTS
RS232 (Port 0)
Terminal card
-ve 5V +ve 0V
RS485 (Port 1)