Message
associated with..
meaning..
..possible action
No periodic
interrupts at
card x
Any Card
Problem with software, the
watchdog will operate the
MCC / MCB (main control
card/board).
Software error will activate a
system reset.
Ignore single occurrence.
Record event in log book.
No response
number x loop y
Loop Processor
Card
There is no communication
with repeat or mimic panel
software.
Power-up the repeat or mimic
panel.
No room on NVM
card
Backplane (with
memory)
User attempts to backup or
save to an NVM that does
not have enough free space
If there is no memory left
then the card 14 located on
Backplane needs to be
initialised
Node double
allocated at
card x
Network Card
Two network cards have
same address.
Keep address unique.
Node found at
Card x
Network Card
Another panel on the
network acknowledged.
-
Node
lost/restored at
Card x
Network Card
There have been 15
missing replies from
another panel.
Check the wiring or check
and reset the panel Network
card to restore.
Not enough RAM
at card x
Any Card
Not enough memory.
Reset the card and ignore
single occurrence. If
necessary replace the card or
add RAM, where applicable.
Nothing found at
Card x
Loop Processor
Card
No devices found on End 1
or End 2.
Check wiring of loop circuit.
NVM initialised
Memory (NVM)-
Backplane
Memory available verified.
-
NVM is not write
protected
Memory (NVM)-
Backplane
Read and write is possible
to the memory card.
Enable protect if required
using the [set up] menu.
NVM is read only
Backplane (with
memory)
User attempts to write to a
hardware write protected
NVM card
Remove the hardware write
protect before writing
Panel in/out of
commissioning
mode
MCC / MCB (main
control card/board)
Commissioning mode
switched ON/OFF.
To manually switch
commissioning mode use the
[Test/Eng] menu.
Panel Label Set
up
MCC / MCB (main
control card/board)
Panel label has been set
from the menu.
-
Panel powerup
MCC / MCB (main
control card/board)
Software reset of system or
there has been a manual
reset of card 0.
If an automatic reset has
occurred than check for
system errors.
Pattern
number x on loop
y channel x
Loop Processor
Card
Sensor has detected an
interesting event eg
fire/fault.
-
Pointer
corrupted at
Card x
Any Card
Software error.
Software errors will activate
a system reset.
Ignore single occurrence.
Record the event in log
book.
Generic Commissioning instructions
108
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Appendix
B
-
M
essage
A
ction
L
ist