Checking device status
To list the status of a device on an allocated loop at the Control
Panel: Press
Menu On/Off
button and then select
[Info]
,
momentarily press
<etc>
to select [
Status]
->
[Device],
enter a
device number, select
[Loop]
, enter the loop number n, select
[Enter]
to view device status information.
0 - Output, I - Input and . signifies not used
Device
digital I / 0
channels
S cubed
0 0 0 0
1- IR control
2 - Tone
3 - Power
4 - Strobe
5
Sounder
. 0 0 .
3 - Low freq.
2 - On/Off
Repeat sounder
. 0 0 .
Interface unit (mains
powered)
all possible
I - input
0 - output
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5-battery
6-mains
Optical
. . . 0
1
Optical heat
. . . 0
1,2
Heat
. . . 0
4
Slave Relay
0 . . 0+R
Slave LED
. . . 0 +L
Beam transmitter
. . . 0
2
Beam receiver
. . . 0
1- raw data
2- average
data
MCP
. . . 0
6
Repeat panel
. . . 0
-
Zonal mimic
. . . 0
-
Device
digital I / 0
channels
Mimic panel
(standard A2 and A4
size)
. . . 0
-
Loop interface
all possible
I - input
0 - output
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5
Single channel
interface unit
I 0 . 0
1,2,5
Loop powered zone
module
I . . 0
1,5
Optical/Heat
Sounder
. 0 0 0
1,2
T-breaker O/S
. . . 0
S-Quads
S-Quad Heat Sensor . . . 0
2
S-Quad Heat Sensor
Sounder
. 0 0 0
2, 5
S-Quad Dual Optical
Heat Sensor
. . . 0
1, 2,4
S-Quad Dual Optical
Heat Sensor Strobe
0 . . 0
1, 2, 4, 5
S-Quad Dual Optical
Heat Sensor
Sounder
. 0 0 0
1, 2, 4, 5
S-Quad Dual Optical
Heat Sensor Speech
Strobe
0 0 0 0
1, 2, 4, 5
S-Quad Dual Optical
Heat Sensor CO
. . . 0
1, 2, 3, 4, 5
S-Quad Dual Optical
Heat Sensor CO
Speech Strobe
0 0 0 0
1, 2, 3, 4, 5
+ Monitored input
6
+ Monitored output
6
Analogue Channel 1 is forward scatter optical smoke sensor
Analogue Channel 2 is heat sensor
Analogue Channel 3 is for CO gas sensor
Analogue Channel 4 is for backward scatter optical smoke
sensor
Analogue Channel 5 reports sounder/flasher/speech faults to
the control panel
Analogue Channel 6 reports monitored input/monitored output
faults/operation to the control panel
"
The correct device type may not be displayed
if the loop circuit has allocation faults.
¨
Check that the device is of the correct type and is
suitable for the area in which it is installed.
¨
Check the digital status of all devices.
¨
On successful allocation
check that the total number of
devices found equals the number installed
. Also there
will be a loop voltage on the unconnected end of the
cable.
Generic Commissioning instructions
50
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Checking
device
status
Loop 1 No.
7 Dual optical/Heat/CO
LB1:C
End1:Hi
End2:Hi
I/O:...0 Anal:1-4
2nd:250 3rd:0 Short delay:0
Zone 1
Zone 1
LED)
,6
Loop on which
the device is installed
Location of the
device on the loop
Device description
Description of
monitored input/LED
attached to the device
Loop breaker
condition
C:closed
Status of End 1
of the device
(high or low)
Status of End 2
of the device
(high or low)
Digital
Input outputs
Analogue channels
used
1:Optical (forward)
2:Heat
3:Gas
4:Optical (Backward)
5:Sounder/Strobe/Speech fault
6:Monitored line or LED
Secondary address
denotes group of devices
Tertiary address
used primarily by
sounders/strobe
Short circuit delay
associated with
number of T breakers
off T breakers
Zone number and label