Repeat indicator panel
Always press the RESET button after setting the switches.
Port 0 is a factory configured to RS485 for connecting Repeat
indicator panel. It is factory set for RS485 at 1200 baud. If
however the port settings were changed then it is possible to
reconfigure Port 0.
"
If there is only one repeat indicator panel
connected to the control panel then an external 24V
power supply is NOT required. Connect the 24V wire
directly to the control panel
"
On the control panel, RS485 Port 2 may be
used to connect repeat indicator panels. You will need
to configure Port 2 for Repeat mode and required baud.
1
2
3
4
5
6
7
8
9
0
+
REL
-
24V
a
b
RS485
ON
1 2 3 4 5 6 7 8
J6
J5
J7
Back cable
entry point
Thinned sections
on sides of enclosure for
cable entry
4 enclosure fixing points
Dual in line switch
Reset
switch
PANEL
MASTER CONTROL
BOARD
Terminals P15 is PORT 0 of
Master Control Board
(Card 0)
The factory default
setting of PORT 0 is set
for
to allow repeat indicator
panel connection
Repeat mode
REPEAT RS485
24V
B
A
0V
P15
REPEAT INDICATOR PANEL 1
a
b
RS485
earth
REPEAT INDICATOR PANEL 4
a
b
RS485
earth
UP TO 4 REPEAT
INDICATOR PANELS
MAXIMUM
S24
RESET
S24
REPEAT INDICATOR PANEL 3
RESET
REPEAT INDICATOR PANEL 2
ON
RESET
REPEAT INDICATOR PANEL 1
ON
RESET
REPEAT INDICATOR PANEL 4
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
S24
1 2 3 4 5 6 7 8
S24
24V
POWER
SUPPLY UNIT
J2
J3
J4
J6
J5
J7
J2
J3
J4
J6
J5
J7
J2
J3
J4
J6
J5
J7
J2
J3
J4
J6
J5
J7
END STATION LINK SETTING
NOTE: IF ONLY ONE REPEAT INDICATOR PANEL
IS CONNECTED TO THE CONTROL PANEL,
THEN THE END STATION LINK CONFIGURATION
MUST BE SET IN THE MANNER SHOWN FOR
REPEAT INDICATOR PANEL 4 BELOW.
+
-
ON
S24
ON
ON
ON
9600 baud
4800 baud
2400 baud
1200 baud
1 2
-
+
24V
-
+
24V
24V