Device
LPCB approved
sensor STATE *
Meets
Heat Sounder (S4-780)
State 0
Class A1 heat
State 5
Class B heat
Dual Optical Heat
Sensor Speech strobe
(S4-711-ST-VO & S4-771)
State 0
Medium optical smoke / Class A1 heat
State 5
Medium optical smoke / Class B heat
State 8
Delayed medium optical smoke / Class A1 heat
Dual Optical Heat CO Sensor
Speech & Strobe
(S4-911-ST-VO)
State 0
Medium optical smoke / Class A1 heat
State 9
Class A1 heat
All S4 range of sensor sounder devices meet CEA GEI 1 - 084 Requirements and test methods for input/output devices for use on
the transmission paths of fire detection and alarm system.
~ Meets following tone settings High tone ( Continuous 933Hz) & Alternate (High 933Hz for 0.25s / low 700Hz for 0.25s)
On initial power-up the system selects
state 0
for all devices.
34xxx Sensors
The following
34xxx sensors
when operating in the state shown below are LPCB approved to the respective standard.
Product number Description
Approval
Compact "O"
Optical sensor
EN 54 : Part 7 #
34710
Optical heat sensor
EN 54 : Part 5 and Part 7 #
34720
Heat sensor
EN 54 : Part 5 #
34770
Optical heat sounder sensor EN 54 : Part 5, part 7 and LPCB requirements #
34800-EN
Manual Call Point
EN54 Part 11
34842-EN
Manual Call Point
EN54 Part 11
¨
If a 34xxx sensor is configured to operate a non LPCB approved state, then this will contravene the LPCB approval.
* - these devices are LPCB approved when operating in the LPCB approved STATE, see table below.
"
All the LPCB states applicable to fire sensors are shown below. The required state is configured during
commissioning and can be configured at the control panel.
Device
LPCB approved sensor
STATE
#
Meets
Optical heat sensor
(34770 and 34710)
State 0
Medium smoke sensitivity with Grade 2 heat
State 8
Smoke sensing with delay + Grade 2 heat
State 12
Grade 1 heat only
State 13
Grade 2 heat only
Heat sensor (34720)
State 0
Default sensitivity
State 1
Grade 1
Heat sounder
(34780)
State 0
Grade 2 heat
State 12
Grade 1 heat
On initial power-up the system selects
state 0
for all devices.
Sounder Strobe
The following
S-cubed Mark 1
range of products are LPCB approved to
EN 54 : Part 3
S3-SN-R, S3-SN-W, S3IP-SN-W, S2IP-SN-R, S2IP-SN-W, S2IP-SN-R3, S2IP-SN-W3, S3-SN-ST-RR, S3-SN-ST-WR,
S3IP-SN-ST-RR, S3IP-SN-ST-WR, S3IP-SN-ST-RW and S3IP-SN-ST-WA.
Interface Units
The following products are approved to
prEN 54 Part 18 : 2005
34410
Zone module (loop powered)
34450
4 Channel Input / Output Interface unit (loop powered)
34415
Single channel Interface unit
Generic Commissioning instructions
10
4188-856_i2_12/06_Generic Vigilon (C VA) Comms.
Product
A
pproval
and
S
tandards