SCANNER SAFETY AND LOCAL CONTROLS
6510020335
26
Figure 21 shows a typical user panel radiation status condition, indicating:
•
the nuclear sensor interlock switch is on, yellow indicator and switch position
•
the basis weight sensor button has been enabled, yellow ring indicator
•
the basis weight shutter was commanded open, overall large red indicator and
smaller red indicator above basis weight enable button
•
the shutter is open, green indicator above radiation symbol is off
Fig. 22.
Unsafe User Panel Radiation Shutter Status
Figure 23 shows a safe working condition indicated by the user panel radiation status
lights. The green, shutter closed indicator is on and the red shutter indicators are all off.
Fig. 23.
Safe User Panel Radiation Shutter Status