System Troubles Register Map
Modbus Communications
360004
0
ANNUN.17 NO ANSWER
8
ANNUN.21 NO ANSWER
1
ANNUN.18 TROUBLE
9
ANNUN.22 TROUBLE
2
ANNUN.18 NO ANSWER
10
ANNUN.22 NO ANSWER
3
ANNUN.19 TROUBLE
11
ANNUN.23 TROUBLE
4
ANNUN.19 NO ANSWER
12
ANNUN.23 NO ANSWER
5
ANNUN.20 TROUBLE
13
ANNUN.24 TROUBLE
6
ANNUN.20 NO ANSWER
14
ANNUN.24 NO ANSWER
7
ANNUN.21 TROUBLE
15
ANNUN.25 TROUBLE
360005
0
ANNUN.25 NO ANSWER
8
ANNUN.29 NO ANSWER
1
ANNUN.26 TROUBLE
9
ANNUN.30 TROUBLE
2
ANNUN.26 NO ANSWER
10
ANNUN.30 NO ANSWER
3
ANNUN.27 TROUBLE
11
ANNUN.31 TROUBLE
4
ANNUN.27 NO ANSWER
12
ANNUN.31 NO ANSWER
5
ANNUN.28 TROUBLE
13
ANNUN.32 TROUBLE
6
ANNUN.28 NO ANSWER
14
ANNUN.32 NO ANSWER
7
ANNUN.29 TROUBLE
15
NETWORK FAIL PORT A
360006
0
NETWORK FAIL PORT B
8
UDACT TROUBLE
1
NETWORK FAILURE
9
UDACT NO ANSWER
2
ADV WALK TEST
10
PROG MODE ACTIVATED
3
CHARGER FAIL
11
LOADING..NO SERVICE
4
GROUND FAULT LOOP 2
12
BASIC WALK TEST
5
STYLE 6 NEG. LOOP 1
13
NFPA 24HR REMINDER
6
STYLE 6 NEG. LOOP 2
14
NVRAM BATT TROUBLE
7
GROUND FAULT LOOP 1
15
Reserved
360007
0
Reserved
8
OPTION MODULE
1
Reserved
9
STYLE 6 ON LOOP 3
2
Reserved
10
AVPS. TROUBLE
3
Reserved
11
NAM CCBE PROG. LOST
4
Reserved
12
MAN. EVAC INITIATED
5
Reserved
13
MAN. EVAC RECEIVED
6
Reserved
14
Reserved
7
Reserved
15
Reserved