CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
110
CGW-MB Parts
The BACnet Feature
8.4 CGW-MB Parts
8.5 System Requirements
The CGW-MB can monitor up to 16 panels. All of these panels should have a combined
maximum of 15,000 objects only. This includes all detectors, monitor modules, control
modules, bell circuits, and so on.
Refer to the panel manual for details about wiring limitations.
Access the configuration web page from a computer in the same IP subnet as the CGW-
MB with latest version of Google Chrome™. JAVA® version 6 or higher must also be
installed and enabled.
8.6 System Architecture
These are connections options for the CGW-MB architecture.
An Internet or Intranet IP network connection is used with both architectures.
8.6.1 IP Restrictions for the CLSS Gateway mainboard
•
Assign a static IP address.
•
Following are not supported:
• Web access through an HTTP proxy server
• Use of a NAT (Network Address Translation)
Other
Products
Unmonitored but network compatible.
• NCA-2
• NCD
• NWS-3
• BACNET-GW-3
• NFN-GW-PC-HNW-2
• NFN-GW-EM-3
• PC NFN CLSS Gateway mainboards:
• NFN-GW-PC-F
• NFN-GW-PC-W
• NFN-GW-PC-HNMF
• NFN-GW-PC-HNSF
• NFN-GW-PC-HNW
• VESDA-HLI-GW
Table 8.1: CLSS-Compatible Equipment List
Type
Equipment
Part Number
Description
HON-CGW-MBB
CGW-MB with enclosure
CGW-MB
CGW-MB board
CGW-BB
CGW-MB enclosure
50160636-001
CGW-MB kit. It includes a 30” NUP cable
and a NOTIFIER lock and key set.
32351718-001
10 ft NUP Serial (RS-232) cable kit
NOTE:
DHCP is supported, but not recommended.
Before using DHCP with LAN for Intranet connection, consult the network
administrator of the Site.