CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
127
BACnet PIC Statement
The BACnet Feature
Supported - Binary Value Object
Present Value
BACnet
Enumeration
Fire Panel State
0
bpv_InActive
Trouble, Device Disabled, Normal
1
Bpv_Active
Activation
Event State
BACnet
Enumeration
BACnet Event
State
Fire Panel State
0
EsNormal
Normal
1
EsFault
Trouble, Device Disabled
2
EsOffNormal
Activation
Reliability
BACnet
Enumeration
BACnet
Reliability
Fire Panel State
0
reNoFaultDet
ected
Activation, Device Disabled, Normal
7
re_Unreliable
Other
Trouble
Status Flags
Boolean
BACnet Status
Flags
Fire Panel State
0,0,0,0
Normal
Normal
1,0,0,0
InAlarm
Activation
0,1,0,0
Fault
Trouble
0,0,0,1
OutOfService
Device Disabled
1,0,0,1
InAlarm,
OutOfService
If device is in Alarm state (
Activation) and also device goes to
disable state(Device Disabled)
0,1,0,1
Fault,
OutOfService
If device is in trouble state
(Trouble)and also device goes to
disable state(Device Disabled)
Out of Service
Boolean
Fire Panel State
0
FALSE
All statuses other than disable
1
TRUE
Device Disabled