
CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
101
System Troubles Register Map
Modbus Communications
460032
0
Reserved
8
NO POWER SUPPLY INST
1
Reserved
9
LOOP 1-2 COMM FAILURE
2
LINK PROTECTOR PRIMARY STATUS
10
LOOP 3-4 COMM FAILURE
3
LINK PROTECTOR SECONDARY
STATUS
11
LOOP 5-6 COMM FAILURE
4
LINK PROTECTOR NOT PRESENT
12
LOOP 7-8 COMM FAILURE
5
EVENT BUFFER 80% FULL / HISTORY
80% FULL
13
LOOP 9-10 COMM FAILURE
6
EBI STATUS
14
TEST PROGRAM UPDATE
7
SOFTWARE MISMATCH
15
Reserved
460033
0
LOOP CONTINUITY TEST FAIL LOOP 1
8
LOOP CONTINUITY TEST FAIL LOOP 9
1
LOOP CONTINUITY TEST FAIL LOOP 2
9
LOOP CONTINUITY TEST FAIL LOOP 10
2
LOOP CONTINUITY TEST FAIL LOOP 3
10
UNPROGRAMMED DEVICE ON LOOP 1
3
LOOP CONTINUITY TEST FAIL LOOP 4
11
UNPROGRAMMED DEVICE ON LOOP 2
4
LOOP CONTINUITY TEST FAIL LOOP 5
12
UNPROGRAMMED DEVICE ON LOOP 3
5
LOOP CONTINUITY TEST FAIL LOOP 6
13
UNPROGRAMMED DEVICE ON LOOP 4
6
LOOP CONTINUITY TEST FAIL LOOP 7
14
UNPROGRAMMED DEVICE ON LOOP 5
7
LOOP CONTINUITY TEST FAIL LOOP 8
15
UNPROGRAMMED DEVICE ON LOOP 6
460034
0
UNPROGRAMMED DEVICE ON LOOP
7
8
IR ENABLED ON LOOP 5
1
UNPROGRAMMED DEVICE ON LOOP
8
9
IR ENABLED ON LOOP 6
2
UNPROGRAMMED DEVICE ON LOOP
9
10
IR ENABLED ON LOOP 7
3
UNPROGRAMMED DEVICE ON LOOP
10
11
IR ENABLED ON LOOP 8
4
IR ENABLED ON LOOP 1
12
IR ENABLED ON LOOP 9
5
IR ENABLED ON LOOP 2
13
IR ENABLED ON LOOP 10
6
IR ENABLED ON LOOP 3
14
TRANSMIT/RECIEVE ERROR ABOVE
LIMIT ON LOOP 1
7
IR ENABLED ON LOOP 4
15
TRANSMIT/RECIEVE ERROR ABOVE
LIMIT ON LOOP 2
Table 7.41: System Troubles Register Map (Continued)